Two numbers decide what an MCCB really is: Icu and Ics. Both are breaking capacities, both are printed on the front of the device, and buyers routinely quote one while meaning the other. The difference is not academic — it decides whether the breaker survives one fault or six, and it moves the price by a step.
This guide explains what each rating measures, how the standard defines the test behind it, and how to pick a rating that matches your actual fault level instead of the biggest number on the catalogue page.
What Icu Actually Means
Icu is the rated ultimate short-circuit breaking capacity. It is the highest fault current the breaker can interrupt, and after that single interruption the breaker is allowed to be unfit for further service. The standard test sequence is O – t – CO: one opening operation, a pause, then a close-open operation on a fault.
After passing, the device must still be safe — no explosion, no door blown open, no live parts exposed — but it does not have to keep carrying its rated current afterwards. That is why Icu is described as “ultimate”: it is a survival limit, not a working rating.
In practice, the Icu number is what appears in bold on the nameplate and in the headline of most datasheets. It is also what gets compared between brands, which is exactly where the confusion starts.
What Ics Actually Means
Ics is the rated service short-circuit breaking capacity, expressed as a percentage of Icu — commonly 50%, 75%, 100%, and occasionally 25% on cheaper ranges. It is tested with a longer sequence: O – t – CO – t – CO. Two full close-open operations on fault, and the breaker must still be capable of carrying its rated current and operating normally afterwards.
That is the number that matters in a real installation, because a breaker does not always see a single fault in its life. A feeder that trips twice on a faulted motor, gets reclosed, and trips again has already exceeded what a 50% Ics device was tested for.
Why the Difference Matters in Service
Consider a 250 A MCCB with Icu = 36 kA and Ics = 50%, so 18 kA service capacity. Your calculated fault level at that board is 22 kA. The breaker interrupts the first fault without damage and looks fine. After that interruption, its contacts and arc chutes have absorbed energy they were never qualified to handle repeatedly — and the second fault may not be interrupted cleanly.
This is not a theoretical failure mode. It is one of the reasons a board passes its type test, passes commissioning, and then fails after two or three fault events in the same year.
| Rating | Test Sequence | After the Test | What It Tells You |
|---|---|---|---|
| Icu | O – t – CO | Safe, not required to continue service | Absolute survival limit |
| Ics (% of Icu) | O – t – CO – t – CO | Must still carry rated current | Repeated fault capability |
| Icm | Peak making current | – | Ability to close onto a fault |
| Icw | Short-time withstand, no opening | Must stay closed | Selectivity and back-up coordination |
Icm is often forgotten. A breaker that can interrupt 36 kA but cannot withstand the peak making current at that fault level will be destroyed at the moment of closing, not opening. For a 36 kA RMS fault, the peak is roughly 2.1 times that at a typical X/R ratio.
How to Match the Rating to Your Fault Level
The calculation order is fixed and short:
1. Get the prospective fault current at the board from the utility or from a short-circuit study. Do not use the transformer’s rated current as a proxy.
2. Add margin for future load growth. Most consultants use 10-20%.
3. Select Icu so that it exceeds that value, then check the Ics percentage.
4. If Ics lands below your fault level, either step up one frame size or accept that the device is a single-fault device — and document it.
For a 400 A distribution board fed from a 630 kVA transformer, fault levels around 20-25 kA are normal. A 36 kA / 50% Ics device gives 18 kA service capacity and is technically undersized for repeated faults, even though its headline number looks comfortable. A 36 kA / 100% Ics device, or a 50 kA frame, is the honest choice.

Both ratings are printed together on the front plate. Reading only the larger number is the most common specifying error, and it survives every audit until the first real fault.
Where Cost Comes From
Going from 50% Ics to 100% Ics at the same Icu usually means: bigger arc chutes, more contact material, stronger trip mechanism, and a larger frame for the same current rating. Expect 15-30% more per device. Going up one Icu step — 36 kA to 50 kA — costs less than most people assume, because the frame is often shared.
The expensive mistake is the reverse: buying a high Icu with low Ics percent and assuming the number on the front covers the installation. It covers the first fault only.

A feeder panel where the MCCB choice sets the fault rating of the whole board. See our circuit breaker buying guide for the frame and trip unit side of the same decision.
Coordination and Back-Up Protection
There are two legitimate ways to use a breaker below the board’s fault level:
Series rating (cascade). A current-limiting device upstream — a fused switch or a higher-class MCCB — is tested with the downstream device as a pair. The combination has a higher rating than the downstream device alone. This works only when the pair is listed together by the manufacturer; mixing brands voids the assumption.
Selectivity. The upstream device is set to trip later than the downstream one, so a fault trips only the feeder breaker. This is a time-current coordination study, not a capacity issue, and it depends on Icw as much as Icu — see protection relay coordination for how the upstream logic is usually implemented.
Both approaches are cheaper than over-sizing every device, but both require documentation. A cascade that was never tested as a pair is not a cascade, it is two breakers hoping for the best.
What to Write on the Enquiry
A single line prevents the whole argument: “MCCB, 250 A, Icu 36 kA, Ics 100% of Icu, Icm as per IEC 60947-2, thermal-magnetic trip.” If you accept 50% Ics, say so explicitly and note the fault level it is rated for.
Then confirm on delivery — nameplate values, not the catalogue. Our MCB vs MCCB comparison covers the smaller frames where the same rating logic applies, and the circuit breaker basics article explains trip unit types.

Inside a feeder compartment: the breaker is only as good as the fault level the board was calculated for. Verify the installed device against the study, not the other way round.
FAQ
Is a higher Icu always better?
No. If Ics stays at 50%, a higher Icu buys a bigger single-fault limit but the same repeated-fault capability. Match both numbers to the study.
Can I use Ics instead of Icu for the calculation?
Ics should exceed the prospective fault current for any feeder expected to see repeated faults. Many specifications now require Ics ≥ 100% of Icu for this reason.
What is Icm and why does it matter?
Icm is the peak making current the breaker can withstand when closing onto a fault. It is typically 2.1 times the RMS fault current at standard X/R and is destroyed-by-closing territory if exceeded.
Do series ratings work across brands?
Only if the manufacturer’s tested combination lists both devices. Untested pairs are not covered, whatever the arithmetic suggests.
How much margin should I add?
10-20% on the calculated fault level is the common practice, more where load growth is expected or where the utility may upgrade the supply.
Does a 50% Ics breaker fail after one fault?
No. It is tested for one interruption and expected to remain safe but not necessarily serviceable. In practice many continue working, but you cannot rely on it for the next fault.
About Electric-GS
Electric-GS assembles LV and MV switchgear in Yueqing, China, and specifies breakers by both Icu and Ics against the fault study for each project. We can review your board schedule and flag devices whose service capacity is below the calculated fault level. Contact info@electricgs.com or WhatsApp +86 135 8897 8050. Related reading: transformer winding resistance checks for the upstream side, and RMU earthing switch interlock for MV switching safety.