GN19-12 Indoor High-Voltage AC Isolating Switch

GN19-12 Indoor High-Voltage AC Isolating Switch

GN19-12(C) indoor high-voltage isolating switch is used in the AC 50Hz power system with rated voltage of 12kV and with rated current of less than  1250A for closing and opening circuit under the voltage without load. The isolating switch can be equipped with a CS6-1 manual operating mechanism and an optional live display device.

Main applications:
GN19-12(C) indoor high-voltage isolating switch is used in the AC 50Hz power system with rated voltage of 12kV and with rated current of less than  1250A for closing and opening circuit under the voltage without load. The isolating switch can be equipped with a CS6-1 manual operating mechanism and an optional live display device.

Technical Parameters:

Model Rated voltage
(kV)
Rated current
(A)
Rated peak
withstand
current (kV)
Rated short-
time withstand  current (kA/4S)
Power
frequency
withstand
voltage for 1
minute (kV)
Lightning
impact voltage
(kV)
GN19-12/400-12.5 12 400 31.5 12.5 P/phase to
phase, P/phase
to earth: 42kV;
O/open
contacts:48
P/phase to
phase, P/phase
to earth: 75kV;
O/open
contacts:85
GN19-12/630-20 630 50 20
GN19-12/1000-31.5 1000 80 31.5
GN19-12/1250-40 1250 100 40
GN19-12C/400-12.5 400 31.5 12.5
GN19-12C/630-20 630 50 20
GN19-12C/1000-31.5 1000 80 31.5
GN19-12C/1250-40 1250 100 40

Operating Conditions:
1.Ambient temperature: Upper limit: +40ºC; Lower limit: -15ºC;
2.The altitude does not exceed 1,000 meters.
3.For relative air humidity, the daily mean is not greater than 95%, and the monthly mean is not greater than 90%;
4.The earthquake intensity does not exceed 8 degrees.
5.Installed in places free of fire, explosive risk, chemical corrosion, and violent vibration.
6.The installation site shall be free of flammable substance, explosive risk, chemical corrosion and violent vibration.
7.Pollution degree 2.
Please contact the manufacturer for customizing those failed to follow the normal working conditions.

Outline and Installation Dimensions:

Fig. 1 GN19-12 Outline dimensions

Fig. 2 GN19-12C Outline dimensions

                                                                              

Fig. 3 Wiring terminal installation dimensions

Model P W V A B C D
GN19-12/400 210 620 868 450 446 185 4x14x24
230 660 908
250 700 948
GN19-12/630 210 620 868 470
230 660 908
250 700 948
GN19-12/100  GN19-12/1250 210 620 868 510 500 196 4x18x28
230 660 908
250 700 948
GN19-12C/400 210 620 868 420 690 185 4x14x24
230 660 908
250 700 948
GN19-12C/630 210 620 868 430
230 660 908
250 700 948
GN19-12C/100  GN19-12C/1250 210 620 868 470 745 196 4x18x28
230 660 908
250 700 948