KYN28A-24 Electrical Circuit Control Monitoring Power Switchgear (hereinafter referred to as “switching device”), suitable for three-phase AC The 50Hz power system is used to receive and distribute electrical energy and control, protect and monitor the circuit. This product conforms to the standard: GB3906-2006 “3.6-40. 5KV AC metal-enclosed switchgear and control equipment”, GB /T11022 “High voltage Common Technical Requirements for Switchgear and Control Equipment Standards”, IEC60298 “AC metal-enclosed switchgear with rated voltage above 1KV and below 52KV Control Equipment”, DL/T404 “Technical Conditions for Ordering Indoor AC High Voltage Switchgear”.
KYN28A-24 Electrical Circuit Control Monitoring Power Switchgear (hereinafter referred to as “switching device”), suitable for three-phase AC The 50Hz power system is used to receive and distribute electrical energy and control, protect and monitor the circuit. This product conforms to the standard: GB3906-2006 “3.6-40. 5KV AC metal-enclosed switchgear and control equipment”, GB /T11022 “High voltage Common Technical Requirements for Switchgear and Control Equipment Standards”, IEC60298 “AC metal-enclosed switchgear with rated voltage above 1KV and below 52KV Control Equipment”, DL/T404 “Technical Conditions for Ordering Indoor AC High Voltage Switchgear”.
Normal use environmental conditions
Project | Unit | Data | ||
Rated voltage | KV | 3.6、7.2、12、24 | ||
Rated frequency | Hz | 50 | ||
Circuit breaker rated current | A | 630、1250、1600、2000、2500、3150、4000 | ||
Rated current of switchgear | A | 630、1250、1600、2000、2500、3150、4000 | ||
Rated short-time withstand current (4s) | KA | 16、20、25、31.5、40、50 | ||
Rated peak withstand current (peak value) | KA | 40、50、63、80、100、25 | ||
Rated short-circuit breaking current | KA | 16、20、25、31.5、40、50 | ||
Rated short-circuit making current (peak value) | KA | 40、50、63、80、100、25 | ||
Rated insulation level | 1min power frequency withstand voltage | Between poles, betweenpoles to ground | KV | 24、32、42、65 |
Fracture | KV | 24、32、48、79 | ||
Lightning impulse withstand voltage(peak value) | Between poles, betweenpoles to ground | KV | 40、60、75、125 | |
Fracture | KV | 46、70、85、145 | ||
Protection leve | The shell is IP4X,and when the door of the next door and circuit breaker room is opened, it is IP4X |
Note: 1. The short-circuit capacity of the current transformer is considered separately;
2. The technical parameters of VS1-24 are detailed in the corresponding samples of our company
Switchgear structure (see Figure 1).
2. Completely metal armored, assembled structure, wide combination schemes.
3. The cabinet body is made of imported aluminum-zinc coated thin steel plate, processed by MINGE machine tools, and adopts advanced
Multi-folding process, connected with blind rivet nuts and high-strength bolts, with high precision, light weight and strong High degree of
accuracy and strong versatility of parts.
4. It can be equipped with VS1-24 series or imported VD4 series vacuum circuit breaker, which has wide applicability and reliability.
High performance, to achieve long-term maintenance-free.
5. The handcart is equipped with working and test positions, and each position has positioning and display devices, which is safe and reliable.
6. All kinds of handcarts can be changed according to modular building blocks to ensure that cars of the same specification can be freely
interchanged, with different specifications Cars must never enter.
7. Installation method of earthing switch
1) Installed in the middle of the cabinet (front-mounted) to facilitate double-sided maintenance after the cabinet (Figure 1-a).
2) Installed at the back of the cabinet (rear-mounted) to save space and area against the wall (Figure 1-b).
8. Current transformer installation method:
1) The cable room at the rear of the cabinet is installed.
2) Hoisting at the bottom of the large curved plate.
9. Up to 9 single-core cables can be installed in the cable room.
10. Each high-pressure chamber has a pressure relief channel to ensure personal safety.
11. The highly reliable interlocking device fully meets the “five prevention” safety requirements.
12. The handcart is transported by a special carrier, which is easy to operate and flexible.
13. The front and rear doors are equipped with observation windows, which can facilitate the observation of the working status of the indoor components
A、Busbar room B、Circuit breaker handcart room C、Cable room. D、Relay instrument room.
1、Shell 2、Branch bus 3、Bus bushing 4、Main bus 5、Static contact device 6、Contact box 7、Current Transformer
8、Earthing switch 9、Cable 10. Lightning arrester 11. Ground bus 12. Loading and unloading partitions 13. Partition (trap)
Height B | 2430 | |
Height A | Rated current of branch small busbar ≤1250A, thermal stability current 40KA | 1000 |
Rated current of branch small busbar ≥1600A | 1000 | |
Height C | Cable in and out | 1810 |
Overhead incoming and outgoing lines | 2170 |