KYN28-24 Metal-claded withdrawable AC metal-enclosed switchgear is a complete set of power distribution equipment for 24kV three-phase AC 50Hz single bus and single bus section system. It is mainly used for power plants, small and medium generators to transmit power, power distribution of industrial and mining enterprises, and secondary substations of electrical industry systems for control, protection, and monitoring. This switchgear meets DL/T404, IEC298, GB3906 and other standards. It has the interlock function to prevent the load-carrying withdraw circuit breaker trolley, prevent the circuit breaker from being closed or opened by mistake, to prevent the circuit breaker from being closed when the earth switch is in the closing position, to prevent entering the live compartment by mistake, and to prevent the earth switch from being closed by mistake.
Overview
KYN28-24 Metal-claded withdrawable AC metal-enclosed switchgear is a complete set of power distribution equipment for 24kV three-phase AC 50Hz single bus and single bus section system. It is mainly used for power plants, small and medium generators to transmit power, power distribution of industrial and mining enterprises, and secondary substations of electrical industry systems for control, protection, and monitoring. This switchgear meets DL/T404, IEC298, GB3906 and other standards. It has the interlock function to prevent the load-carrying withdraw circuit breaker trolley, prevent the circuit breaker from being closed or opened by mistake, to prevent the circuit breaker from being closed when the earth switch is in the closing position, to prevent entering the live compartment by mistake, and to prevent the earth switch from being closed by mistake.
Model Meaning
Normal Use Conditions
Ambient air temperature: -15℃~+40℃.
Humidity conditions: Daily average relative humidity: ≤95%.
The daily average water vapor pressure ≤2.2kPa.
The monthly average relative humidity is 90%.
The monthly average water vapor pressure is 1.8kPa.
Earthquake intensity: ≤8 degrees. Horizontal acceleration: 0.3g. Vertical acceleration: 0.15g.
Environmental conditions: suitable for Grade 3 dirty places
Installation location: indoor
Installation method: anchor bolts, welding
Feature
Reliable “Anti-5” Mechanical Latch, Convenient and Safe Maintenance
Provides Middle Rolling and Floor Roiling Two Different Withdrawble Types, Can Meet All Our Customers’ Technical Requirements and Operating Features
Both Vcb of Zn85-40.5/Vs1-40.5 Developed by Our Company and Vd4, Vb2 and 3ah Manufactured by Other Companies Around The World Can be Matched with The Switchgear
Technical Parameter
Item | Unit | Data | |
Rated voltage | KV | 13.8, 15, 17.5, 20, 22, 24 | |
Rated insulation level | 1min.P.F. withstand voltage (phases to ground/gaps) | KV | 50/60 |
Lightning impulse withstand voltage (phases to ground/gaps) | KV | 125/145 | |
Rated frequency | Hz | 50/60 | |
Rated current | A | 630, 1250, 1600, 2000, 2500, 3150 | |
Rated short-time withstand current (4s) | KA | 16, 20, 25, 31.5, 40, 50 | |
Rated peak withstand current※ | KA | 40, 50, 63, 80, 100, 125 | |
Protection class | Enclosure: lP4X ,IP2X (VCB Door opened) | ||
Outline dimension (width×depth×height) | mm | 1000(800)×1800×2400 | |
Weight | kg | 840-1500 |