GSM1E series moulded case circuit breaker is one of the new circuit breakers researched and developed by us with advanced international technology.It is suitable for AC 50/60Hz circuit breaker with rated working voltage 690V and below and with setting current ranged 12.5A to 1600A for infrequent conversion of line and for infrequent starts of motor.
This series of circuit breaker can be vertically installed (vertical installation) and horizontal installed (lateral installation).

Working environment conditions:

1.1 Ambient air temperature: -5℃ ~ +40℃; the mean temperature within 24h does not exceed +35℃; please contact the manufacturer when the ambient air temperature exceeds +40℃ or below -5℃;

1.2 Installation altitude: ≤2,000 meters;

1.3 The relative air humidity does not exceed 50% at the maximum temperature +40℃, and a higher relative humidity is allowed at a low temperature; the mean temperature does not exceed +25℃ in the wettest month, and the maximum mean relative humidity of that month does not exceed 90%. Necessary measures are taken for condensation occurred occasionally due to temperature changes;

1.4 Installed in places whether there is no impact vibration or rain and snow invasion;

1.5 Installed in places whether there is no explosive or hazardous medium, and there is no enough gas or conductive dust to cause corrosion to the metal or damage to the insulation;

1.6 1, 3, 5, and LINE are connected to the power side; 2, 4, 6, LOAD are connected to the load side; the circuit breaker can be installed vertically (vertical installation), and can be installed horizontally (lateral installation); reverse connection is prohibited;

1.7 Pollution degree: 3;

1.8 The installation category of main circuit is III, and of the auxiliary circuit and control circuit not connected to main circuit is II;

1.9 The external magnetic field near the circuit breaker installation site shall not exceed 5 times earth’s magnetic field in any direction;

1.10 Please handle the product with care, do not put it upside down and avoid severe collision during transport.

Basic   parameters
Frame current Inm(A) 100 125 160 250 320 400
Number of poles 3P, 3P+N, 4P
Frequency (Hz) 50/60
Rated wroking voltage Ue(V) 380/400/415  500/550     660/690
Rated insulation voltage Ui(V) 1000
Rated impulse withstand voltage Uimp (kV) 8 12
Rated current   range In (A) 32AF:12.5-32 32AF:12.5-32 63AF:25-63 200AF:80-200 200AF:80-200 300AF:120-300
63AF:25-63 63AF:25-63 125AF:50-125 250AF:100-250 250AF:100-250 315AF:125-315
100AF:40-100 125AF:50-125 160AF:63-160 320AF:125-320 400AF:160-400

 

Basic   parameters
Frame current Inm(A) 630 630s 800 1250 1600
Number of poles 3P, 3P+N, 4P
Frequency (Hz) 50/60
Rated wroking voltage Ue(V) 380/400/415  500/550     660/690
Rated insulation voltage Ui(V) 1000
Rated impulse withstand voltage Uimp (kV) 12
Rated current   range In (A) 400AF:160-400 400AF:160-400 630AF:250-630 800AF:315-800 1250AF:500-1250
500AF:200-500 500AF:200-500 800AF:315-800 1000AF:400-1000 1600AF:630-1600
630AF:250-630 630AF:250-630 1250AF:500-1250