GSLY-C Surge protective devices

GSLY-C Surge protective devices

GSLY-C series surge protective device (hereinafter referred to as SPD) has various protection modes such as
phase-to-phase, phase-to-earth, phase-to-neutral, neutral-to-earth, and their combinations; it is suitable for
AC 50/60Hz TT, IT, TN-S, and TN-C-S power supply system (or communication system) with voltage 380V
and below for protection of indirect thunder and lightning, direct thunder and lighting or other instantaneous
overvoltage and overcurrent surge for more effective electricity safety

Number of poles 1P、2P、3P、4P 1P、1P+N、2P、3P、3P+N、4P 1P、2P、3P、4P
Rated frequency (Hz) 50-60
Grid operational voltage 220/380
Un (V)
Max. Continuous operating current Uc (V) 385 385
Voltage protection grade ≤3.5 ≤3.0 ≤2.5 ≤2.3 ≤2.0 ≤1.8 ≤1.5 ≤2.2 ≤1.8
Up (kV)
Max. Discharge current 160 120 100 80 60 40 20 Iimp25 Iimp15
Imax (kA)
Nominal discharge current 100 70 60 40 30 20 10 30 20
In (kA)
Response time Ta (ns) 100 100 25 25 25 25 25 100 100
L/N recommended diameter of connecting wire (mm) 25,35 16,25 16,25 16,25 16,25 10,16 10,16 25 16
PE recommended diameter of connecting wire (mm) 35 25,35 25,35 25,35 25,35 25 25 35 25
Matched fuse or circuit breaker(A) 63,125 63,100 63,100 32,63 32,63 25,32 16,25 63,125 32,63
Protection grade B B B B B C D B B
Test grade Class II test (8/20 μs) Class I (10/350μs)