GSM1 series moulded case circuit breaker

GSM1 series moulded case circuit breaker

GSM1 series moulded case circuit breaker is a new type of circuit breaker developed with international advanced technology platform. It is suitable for power distribution protection in AC 50/60Hz, circuits with the rated working voltage ≤ 690V, and can also be used for occasional circuit switch and startup of motor.
This series circuit breaker is equipped with overload and short circuit protection devices. This series circuit breaker may be installed vertically (i.e., vertical installation) or horizontally (i.e., horizontal installation).

Working environment conditions:

1.1 Ambient temperature

1.1.1 Normal working temperature is -5°C- +30°C, working temperature limit is -40°C – +70°C.

1.1.2 Derate according to the sample requirements when the temperature is <-5°C or > +30°C (see Table 11 for details).

1.2 Installation category

1.2.1 It is category-III for the main circuit and category- II for remaining auxiliary circuits.

1.3 Pollution class: 3

1.4 Altitude: 2,000 m, derating according to the sample requirements when above 2,000 m (see Table 10 for details).

1.5 Atmospheric conditions

1.5.1 The relative humidity is not more than 50% when the ambient temperature is +40°C;

1.5.2 A higher relative humidity is allowed at the lower temperature.

For example, the relative humidity may be 90% at +20°C. Special measures shall be taken for condensation due to temperature changes.

1.6 Shock and vibration

1.6.1 Withstand mechanical vibration with the frequency of 2Hz-13.2Hz, displacement of ±1mm and mechanical vibration with the frequency of 13.2Hz-100Hz and accelerated velocity of ±0.7g

Basic parameters
Frame current 63 125 160 250 320
Rated working voltage Ue(V) AC230/240、
AC380/400/415、AC660/690
AC230/240、
AC380/400/415、
AC660/690
AC230/240、
AC380/400/415、
AC660/690
AC230/240、
AC380/400/415、
AC660/690
AC230/240、
AC380/400/415、
AC660/690
Rated insulation voltage Ui(V) 800 800 1000 1000 1000
Rated impulse withstand voltage Uimp(kV) 8 8 8 12 12
Rated frequency Hz AC( 50/60Hz)
Rated current In(A) 10、 16、 20、 25、 32、 40、50、 63 10、 16、 20、 25、 32、 40、50、 63、 80、 100、 125 16、 20、 25、 32、 40、 50、60、 63、 70、 75、 80、 100、125、 140、 150、 160 100、 125、 140、 150、 160、170、 180、 200、 225、 250 100、 125、 140、 150、 160、170、 180、 200、 225、 250、270、 280、 300、 315、 320

 

Basic  parameters
Frame current 400 630 630
large volume
800 1250 small  volume 1250
Rated working voltage Ue (V) AC380/400/415、
AC660/690
AC380/400/415、
AC660/690
AC400/415
AC660/690
AC380/400/415
AC660/690
AC400 AC400
Rated insulation voltage Ui (V) 1000 1000 800 1000 800 800
Rated impulse withstand voltage
Uimp(kV)
12 12 8 12 12 12
Rated frequency Hz AC( 50/60Hz) AC( 50Hz) AC( 50/60Hz) AC( 50Hz) AC(50Hz)
Rated current In(A) 250、 280、 300、 315、320、 350、 380、 400 400、 450、 500、 550、600、 630 400、 500、 630 630、 700、 800 630、 700、 800、 1000、 1250